APT3100 Smart Pressure Transmitter Operation Manual M3100-EO1G
29
Duon System Co.,Ltd.
4.7.4 Wiring
▲ Warning
Explosion can result in death or serious injury:
◈
Do not remove the transmitter covers in explosion environments when the circuit is alive.
◈ Before connection HHI in explosion zone, confirm that the configure device has to be installed by
intrinsic safety regulations.
◈ Both transmitter covers must be fully engaged to meet explosion proof requirements
A. Loop Configuration
AUTROL Series Transmitters use a two-wire system for power supply, 4~20mA analog signal
transmission and HART digital transmission.
DC Power Supply is required for the transmitter loop. The Transmitter and distributor are
connected as shown below.
(1) Non-Explosionproof / Flameproof Type
(2) Explosionproof Type